Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.11.2.1.5(b) x The counterweight is touching the spring buffer when the elevator travels to the top floor. The hoist ropes shall be shortened to provide a minimum run-by of 6 inches. Reinspection required in 30 days. 4/9/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Replace defective car top roller guide assembly guide rollers. 5/20/2025