Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)4 Elevator machine room cannot be used for storage. 5/3/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Written maintenance control program shall be kept on site for each elevator. 5/3/2024
MO Minimum : Elevators (I) - Pits (I)1 Pit is full of water 5/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Car top shall be cleaned of wood debris 5/18/2024
MO Minimum : Elevators (A) - Hoistways (A)13 Hoistway enclosure has been altered, vent in top of hoistway has been blocked with wood material. Retain original integrity of hoistway 5/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Car top shall be cleaned of wood debris. 5/28/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. 5/28/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher is expired (2017) in machine room. 2/7/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Updated maintenance records needed on site. 2/7/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not working. 7/23/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. 4/30/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The elevator ADA phone inside the elevator is not working, needs repaired. Re-inspection required 5/2/2024