Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 2/3/2026
MO Minimum : Elevators (I) - Pits (I)1 Clean the elevator pit of debris. 2/3/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 2/3/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates A data plate that indicates the code and edition in effect at the time of installation shall be provided. Data plate shall read Missouri Minimums. 2/3/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods There is an octagon box located on top of the car that requires a cover. 2/3/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. 2/3/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State Operating Certificate is missing from the machine room. 2/3/2026
MO Minimum : Elevators (H) - Machine Rooms (H)8 The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. 2/3/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation The roof is leaking onto the machine brake. Unit left shut down until the roof is repaired. 1/14/2020
MO Minimum : Elevators (H) - Machine Rooms (H)4 The machine room shall be cleaned of dirt, dust and grease. Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored therein. 2/3/2026
MO Minimum : Elevators (H) - Machine Rooms (H)7 There is an octagon electrical box in the ceiling of the machine room with exposed wired, a cover shall be installed. 2/3/2026
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) The hoisting ropes and governor rope data tags are missing. 2/3/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate There is no state operating certificate. 2/3/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The fire extinguisher is expired. 2/3/2026
MO Minimum : Elevators (A) - Hoistways (A)16 Replace missing cover on octagonal box on car top, wires are exposed. 1/30/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete. Governor spin test, pullout/pullthru, break test w/ 125% load, car buffer test w/ full load, buffer test, and set safties W/ full load reamain for cat 5 test.. 3/6/2026
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x x Pull thru measured 220# governor, data tag stated minimum pull thru of 400#. Governor must be repaired, adjusted, and sealed, or replaced and re-inspected. 3/6/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Rope used as a connection from the safety to the governor rope, including rope wound on the safety-rope drum, shall be not less than 9.5mm(0.375 in.) in diameter, shall be made of metal, and shall be corrosion resistant. The factor of safety of the rope shall be not less than 5. Tiller-rope construction shall not be used. 3/9/2023
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x x Governor rope is rubbing on concrete floor. Take corrective action. Elevator Red Tagged. 5/25/2023