Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors The car floor is separating making it difficult to wind-up safety rope. Take corrective action as needed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light shall work. 1/23/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.20 - Governor rope 2.18.5 x A rope data tag is missing on the governor rope. 3/9/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 There is an octagon electrical box in the ceiling of the machine room with exposed wired, a cover shall be installed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State Operating Certificate is missing from the machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 8.11.2.1.2(k) The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) Rope data tags are missing on the hoist ropes. 2/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.8 - Hoistway enclosure 8.11.2.1.4(h) Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction to its full height. There is an opening at the top of the hoistway, that opens into an occupied space.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean the elevator pit of debris.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces The machine room shall be cleaned of dirt, dust and grease. Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored therein.