Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code Repair machine room lighting. 9/4/2020
A17.1-1996 : Elevators 2.33 - Tanks 1206.5b Remove scavenger pump from pit. The amount of oil leakage cannot be monitored. 1/18/2022
A17.1-1996 : Elevators 2.33 - Tanks 1206.5b Remove scavenger pump from pit. The amount of oil leakage cannot be monitored.
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is flooded with water, pit should be kept clean & dry.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code Repair machine room lighting. 8/20/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) - Phase II sign missing in car. 8/20/2019
MO Minimum : Elevators (A) - Hoistways (A)16 Cover all uncovered electrical boxes. 9/4/2020
A17.1-1996 : Elevators 3.17 - Door and gate equipment 1001.2(c)(23) Repair lower panel section of bi-parting doors at both lower landings, care side. Door skin separating from trucking sill. 9/4/2020
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Repair or replace cab emergency lighting. 9/21/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete because elevator broke down, only thing that was completed was fire service. Re-inspection required 6/9/2023
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.1 Examination and Maintenance x x Packing is bad. Piston is worn past holding the packing, replace jack 10/25/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 11/9/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x All phases of fire service and all initiating devices shall be tested. 11/9/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency power operation shall be tested. 11/9/2024