A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
Repair machine room lighting.
|
9/4/2020
|
A17.1-1996 : Elevators
|
2.33 - Tanks
|
1206.5b
|
|
|
Remove scavenger pump from pit. The amount of oil leakage cannot be monitored.
|
1/18/2022
|
A17.1-1996 : Elevators
|
2.33 - Tanks
|
1206.5b
|
|
|
Remove scavenger pump from pit. The amount of oil leakage cannot be monitored.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit floor is flooded with water, pit should be kept clean & dry.
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
Repair machine room lighting.
|
8/20/2019
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)(12) -
|
|
|
Phase II sign missing in car.
|
8/20/2019
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Cover all uncovered electrical boxes.
|
9/4/2020
|
A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
1001.2(c)(23)
|
|
|
Repair lower panel section of bi-parting doors at both lower landings, care side. Door skin separating from trucking sill.
|
9/4/2020
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Repair or replace cab emergency lighting.
|
9/21/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test incomplete because elevator broke down, only thing that was completed was fire service. Re-inspection required
|
6/9/2023
|
A17.1-2016 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.5.1 Examination and Maintenance
|
x
|
x
|
Packing is bad. Piston is worn past holding the packing, replace jack
|
10/25/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
11/9/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.10 Acceptance Inspection and Test
|
x
|
|
All phases of fire service and all initiating devices shall be tested.
|
11/9/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency power operation shall be tested.
|
11/9/2024
|