Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: - The visual signal device did not light in the car when phase I was activated. Reinspection required. 2/23/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. 2/23/2021