Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | The testing has not been completed on the elevator at this time. The Fireman’s Emergency Service operation shall be performed before the inspection is completed. | 2/5/2021 | |
MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | x | Upon performing the required annual pressure test, the hydraulic cylinder of this elevator was having a significant amount of oil loss in the system. The elevator was locked out of service until the system is repaired. | 2/5/2021 |