Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Operation of elevators equipped with standby or emergency power shall be tested to determine conformance with the applicable requirements. 8/11/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x Detector edge shall work with cab lighting off. Door safety circuit cannot be wired to a lighting circuit. 8/6/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Detector edge shall work with cab lighting off. Door safety circuit cannot be wired to a lighting circuit. Note: Elevator is about to undergo modernization and violation to be corrected at that time.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The emergency phone is not working. It dials out, but no one answers. 11/20/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self-closing and self-locking.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 8/24/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The fire extinguisher is expired. 12/27/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates COP shall have car number displayed (multiple units onsite).
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Runby (Re-Inspect) x x Ropes shall be shortened to allow activation of top final before full counterweight buffer compression, resulting in loss of traction. Elevator Red Tagged. 8/6/2024