MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room access door needs to be self-locking and non-defeatable
|
5/11/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room access door needs to be self-closing
|
5/11/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Replace missing cieling tile in machine room. Cables not related to elevator equipment are hanging down into machine room where cieling tile is missing
|
5/11/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light does not illuminate, and emergency bell does not operate without normal power.
|
10/13/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.7 Cleaning of Hoistway and Pit
|
|
|
Remove standing water in elevator pit. Sump pump is not operating.
|
5/11/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light and bell do not operate
|
3/15/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Door reopening device is connected to the car lighting circuit. Car lighting shall be on a dedicated circuit.
|
5/11/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Provide a cover for the sump hole in the pit. cover shall be of non-flammable material, allow water to flow through it, and withstand 250 pounds of weight
|
9/4/2024
|