Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Repair inoperable alarm bell. Recommend addition of emergency phone. 12/15/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x Firefighters service Phase I does not work. 12/15/2020
MO Minimum : Elevators (F) - Electrical Switches (F)9 Provide feeder location on main line disconnect and 110v disconnect. 2/2/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.5 Code Data Plate Provide code data plate. 2/2/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Provide anti-rotation of hoist ropes. 2.27 2/2/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Provide on-site maintenance records. 2/2/2021