A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
A number of machine room lighting fixtures were not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel.
|
|
A17.1-1996 : Elevators
|
4.2 - Hoistway doors
|
110
|
|
|
The hoistway doors have not had the fire retaining tabs installed on them. Fire retaining tabs are required to keep the hoistway door intact in case of extreme heat conditions. Install fire retaining tabs on all hoistway doors.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
The car door operator belt is cracked in a number of locations and shall be replaced.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Door open button not operational during fire service test, needs repaired or replace. Re-inspection required
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
x
|
x
|
Fireman's Phase II failed.
|
8/15/2019
|