Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Door open button not operational during fire service test, needs repaired or replace. Re-inspection required 6/19/2025
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Yes Yes Fireman's Phase II failed. 8/15/2019
A17.1-1996 : Elevators 4.2 - Hoistway doors 110 No No The hoistway doors have not had the fire retaining tabs installed on them. Fire retaining tabs are required to keep the hoistway door intact in case of extreme heat conditions. Install fire retaining tabs on all hoistway doors.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting No No A number of machine room lighting fixtures were not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No The car door operator belt is cracked in a number of locations and shall be replaced.