Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered in oil. The elevator pit shall be kept clean and dry. 7/24/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 3.18 The hydraulic cylinder gland packing is leaking excessively and shall be replaced. 7/24/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) There are no floor identification numbers on the backside of the hoistway doors. 7/24/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.6.4.13 Fire tabs on 3rd floor hoistway door gibb are not turned down, needs repaired 10/17/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed. Perform test on or before next annual inspection. 6/15/2021