A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
Fire extinguisher needs to be serviced.
|
7/14/2020
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light shall work.
|
1/28/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm bell shall work.
|
1/28/2020
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
A number of machine room lighting fixtures were not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel.
|
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
101.5b
|
|
|
The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller.
|
|
A17.1-1996 : Elevators
|
4.2 - Hoistway doors
|
110
|
|
|
The hoistway doors have not had the fire retaining tabs installed on them. Fire retaining tabs are required to keep the hoistway door intact in case of extreme heat conditions. Install fire retaining tabs on all hoistway doors.
|
|
A17.1-1996 : Elevators
|
3.2 - Car top light and outlet
|
204.7
|
|
|
The car top inspection light/fixture did not operate. Repair fixture/light for proper operation and illumination for maintenance/emergency personnel.
|
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
x
|
|
Replace suspension rope due to reduced diameter. Re-inspection required in 90 days
|
9/1/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
x
|
|
Regroove sheave to accommodate new hoist ropes. Sheave is worn causing ropes to wear unevenly. Re-inspection required
|
9/1/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
One pit light is inoperable and shall be repaired.
|
|