Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting A number of machine room lighting fixtures were not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency alarm bell shall work. 1/28/2020
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light shall work. 1/28/2020
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) Fire extinguisher needs to be serviced. 7/14/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) One pit light is inoperable and shall be repaired.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x Regroove sheave to accommodate new hoist ropes. Sheave is worn causing ropes to wear unevenly. Re-inspection required 9/1/2023
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) x Replace suspension rope due to reduced diameter. Re-inspection required in 90 days 9/1/2023
A17.1-1996 : Elevators 3.2 - Car top light and outlet 204.7 The car top inspection light/fixture did not operate. Repair fixture/light for proper operation and illumination for maintenance/emergency personnel.
A17.1-1996 : Elevators 4.2 - Hoistway doors 110 The hoistway doors have not had the fire retaining tabs installed on them. Fire retaining tabs are required to keep the hoistway door intact in case of extreme heat conditions. Install fire retaining tabs on all hoistway doors.
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller.