Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)6 Car would still run on car top inspection with gate open. Reinspection Required. 10/23/2019
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not work. 11/1/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not work, no power 11/1/2023
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) x Suspension ropes have several broken lays and are undersized. 10/23/2019