A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide written maintenance control program for on-site review.
|
9/26/2025
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Provide MCP.
|
9/26/2025
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.11.3.1.1(q)
|
x
|
|
Battery backup lowering unit not working correctly.
|
8/10/2023
|