ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.9 - Floor and emergency identification numbering
|
8.11.2.1.3(o)
|
|
|
There are no floor identification numbers on the backside of the hoistway doors.
|
6/1/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV needs to be tested on or before next annual inspection.
|
6/15/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13
|
|
|
Fire tabs on 2nd & 4th floor hoistway door gibbs are not turned down, needs repaired
|
10/17/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.5.2 Collection of Oil Leakage
|
x
|
|
Cylinder head packing is leaking excessively, needs to be replaced. Re-inspection required
|
2/7/2023
|