MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Traveling cable is split in several spots due to age. Repair/replace traveling cable. 5.5
|
8/17/2018
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell not working
|
7/15/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
x
|
|
Hydraulic pump is leaking hydraulic fluid, needs repair. Re-inspection required
|
3/28/2023
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit lights are not working
|
1/23/2025
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Elevator pit light does not work
|
1/23/2025
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
The sump pump in the pit shall have a non combustible cover
|
1/23/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
The rear door operator belt on the elevator car is worn and shall be replaced.
|
8/11/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
A hoistway door interlock cover is missing on the GR landing and shall be replaced.
|
8/11/2025
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit floor is covered in oil. The elevator pit shall be kept clean and dry.
|
8/11/2025
|