Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. 9/19/2024
conversion conversion conversion - reinspect Yes No Hold position phase 2 fire service 12/4/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) Yes No Disabled car door restrictor. 1/14/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No OSV not sealed. Perform OSV test on or before next annual inspection. 10/25/2022
MO Minimum : Elevators (H) - Machine Rooms (H)9 No No Reverse phase relay needs to be installed to prevent reverse operation of the motor or loss of phase. 10/25/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No The signage for “In Case of Fire Use Stairs” is missing. Install signage that conforms to the building code this elevator was installed to meet. 10/25/2022
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. 10/25/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. 10/25/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone is not working. Re-inspection required 11/25/2025