MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV not sealed. Perform OSV test on or before next annual inspection.
|
10/25/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)9
|
|
|
Reverse phase relay needs to be installed to prevent reverse operation of the motor or loss of phase.
|
10/25/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The signage for “In Case of Fire Use Stairs” is missing. Install signage that conforms to the building code this elevator was installed to meet.
|
10/25/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required.
|
10/25/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed.
|
10/25/2022
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed.
|
9/19/2024
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Hold position phase 2 fire service
|
12/4/2018
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)12 (Door open zones)
|
x
|
|
Disabled car door restrictor.
|
1/14/2020
|