Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 12/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2 On-Site Documentation A code compliant MCP and all the on-site documentation required shall be provided in the machine room. 3/12/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/12/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. 3/12/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x A test of the relief valve shall be performed. 10/11/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.7 Record of Oil Usage A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. 3/12/2024
MO Minimum : Elevators (A) - Hoistways (A)16 Exposed wiring in overhead shall be enclosed in conduit or raceway. 2/20/2020
MO Minimum : Elevators (A) - Hoistways (A)16 Exposed wiring in overhead shall be enclosed in conduit or raceway. 2/20/2020
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Fire service phase one bypass shall work as required by CSR 40-5.065(S1). Note: Phase one hall key switch does not return the elevator to automatic operation as required. 2/20/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Phase one and two operating instructions shall be posted near their associated key switches. 3/12/2024
MO Minimum : Elevators (H) - Machine Rooms (H)4 Remove all non-elevator related equipment and materials from the machine room. 3/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Repair or replace the broken stop on the door operator. 12/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The fire service phase 1 key switch shall be legible. 2/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The fire service phase 1 key switch shall be legible. 2/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The fire service phase 2 key switch in the car shall be legible. 2/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The fire service phase 2 key switch in the car shall be legible. 2/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit The hoistway needs to be cleaned. 3/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The in car emergency alarm bell shall be operational on auxiliary power. 2/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The in car emergency alarm bell shall be operational on auxiliary power. 10/11/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The in car emergency lights shall be operational. 10/11/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The in car emergency lights shall be operational. 2/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 1/4/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-locking and self-closing. 2/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The overspeed valve in the pit shall be tagged. 2/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The overspeed valve in the pit shall be tagged. 2/20/2020
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. Remove oil from the pit floor. 2/20/2020
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. Remove oil from the pit floor. 2/20/2020
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. 12/10/2021
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. Clean the pit. 3/12/2024
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept free of dirt, rubbish, oil, and grease. 3/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The two-way communication means shall provide on demand to authorized personnel, information that identifies the building location and elevator number and that assistance is required. Note: This elevator has had a new in-car telephone installed. The phone is equipped and programmed to transmit location data. The phone is reporting this elevator as the only elevator in the building which is incorrect. It shall be re-programmed to identify it as elevator number one. 2/20/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records There is no MCP on-site. Provide a code compliant MCP and all other required documents. 3/12/2024