Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work, needs repair. Re-inspection required 5/26/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Rear car door restrictor does not work on battery back up, needs repair. Re-inspection required 5/26/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Lighting in machine room shall be at least 10 ft candles
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Lights in machine room shall not be less than 10 foot candles.
MO Minimum : Elevators (H) - Machine Rooms (H)9(A) There is no protection found on elevator to prevent accidental phase reversal or phase loss. Provide motor phase reversal on elevator power supply.