MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Lighting in machine room shall be at least 10 ft candles
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Lights in machine room shall not be less than 10 foot candles.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab does not work, needs repair. Re-inspection required
|
5/26/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Rear car door restrictor does not work on battery back up, needs repair. Re-inspection required
|
5/26/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)9(A)
|
|
|
There is no protection found on elevator to prevent accidental phase reversal or phase loss. Provide motor phase reversal on elevator power supply.
|
|