Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Label all interface cabinets with description of operation in the machine room. (To be re-inspected at completion of MOD on SID 8215)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Label all interface cabinets with description of operation in the machine room. 7/12/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power shall be tested. (To be re-inspected at completion of MOD on SID 8215)
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power shall be tested. 7/12/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Remove phone button/communication loss panel @ 2. (To be re-inspected at completion of MOD on SID 8215)
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) x Remove phone button/communication loss panel @ 2. 7/12/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x All FAID shall be tested. 7/12/2025
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x Verify main and lighting fuses for proper rating and face out. 7/12/2025
A17.1-2016 : Elevators 2.14 - Code data plate 8.9 x Install proper MOD/Alteration data tag. (To be re-inspected at completion of MOD on SID 8215)
A17.1-2016 : Elevators 2.14 - Code data plate 8.9 x Install proper MOD/Alteration data tag. 7/12/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x Machine room shall have at least 1 GFCI. (To be re-inspected at completion of MOD on SID 8215)
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine room lighting shall work and shall be at least 19fc. (To be re-inspected at completion of MOD on SID 8215)
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x Machine room shall have at least 1 GFCI. 7/12/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine room lighting shall work and shall be at least 19fc. 7/12/2025