A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.1
|
x
|
|
Verify main and lighting fuses for proper rating and face out.
|
7/12/2025
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
All FAID shall be tested.
|
7/12/2025
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Remove phone button/communication loss panel @ 2.
|
7/12/2025
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power shall be tested.
|
7/12/2025
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
Machine room shall have at least 1 GFCI.
|
7/12/2025
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Machine room lighting shall work and shall be at least 19fc.
|
7/12/2025
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.9
|
x
|
|
Install proper MOD/Alteration data tag.
|
7/12/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
Label all interface cabinets with description of operation in the machine room.
|
7/12/2025
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
x
|
|
Remove phone button/communication loss panel @ 2. (To be re-inspected at completion of MOD on SID 8215)
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power shall be tested. (To be re-inspected at completion of MOD on SID 8215)
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
Machine room shall have at least 1 GFCI. (To be re-inspected at completion of MOD on SID 8215)
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Machine room lighting shall work and shall be at least 19fc. (To be re-inspected at completion of MOD on SID 8215)
|
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.9
|
x
|
|
Install proper MOD/Alteration data tag. (To be re-inspected at completion of MOD on SID 8215)
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
Label all interface cabinets with description of operation in the machine room. (To be re-inspected at completion of MOD on SID 8215)
|
|