Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x In car emergency telephone shall work. 10/30/2018
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 10/24/2019
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 11/3/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 8/11/2023
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) Machine room is only for elevator materials. Remove all non-elevator related materials.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
A17.1-1996 : Elevators 1.3 - Operating control devices 210.1a The hall call buttons shall be accessible. Note: Buttons are currently taped over.
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x x 2-way communication device shall work (with and without main power) and give proper location. Violation cited originally on 12/19/22 and still not operational. Elevator is Red Tagged. 8/29/2023
A17.1-1996 : Elevators 1.3 - Operating control devices 210.1a The hall call buttons shall be accessible. Note: Buttons are currently taped over as a "child-proof" measure. Hall calls shall be of proper design and construction. This is a multi-year self certify violation. If not complied with prior to the next annual inspection, the violation will require a re-inspection.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Compliant/required documentation & MCP shall be kept in equipment room (neat/organized and not on car top) including wiring diagrams, oil log, and fire service log, recorded monthly. Not present in the machine room at this time.
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 Machine room cab light disconnect shall work properly and be of a lockable style. Currently unable to turn off cab lights due to damaged switch.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Machine room shall have proper fire extinguisher and shall have a current test tag. Note: Extinguisher is expired.