Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No Pit shall be cleaned
A17.1-1996 : Elevators 3.1 - Top-of-car stop switch 210.2(h) Yes No Top of Car inspection station down button shall be repaired
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b No No Machine room air conditioner shall function to keep controllers at manufacturers recommended temperature.
A17.1-1996 : Elevators 1.4 - Sills and car floor 204.2(a) Material for Car Enclosure Linings, and floor Coverings. No No Car floor (diamond plate) shall be secured to prevent trip hazard.
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 107.1a Yes No Runby is less than 1". Hoist Ropes shall be shortened.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation No No Maintenance Control Program (MCP) shall be kept on site.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Pit light shall be repaired
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 No No Handiboxes in machine room shall have covers to enclose wiring.
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors Yes No The front and rear car door restrictors shall be operational. 10/12/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 10/12/2021
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No The in car emergency lighting shall be operational. 10/12/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f Yes No Phase 2 fire service shall operate properly. 10/12/2021
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) No No The machine room shall be provided with a natural or mechanical means to control temperature and humidity in the range specified by the elevator manufacturer. 12/1/2021
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) No No Access to the machine room door shall not be blocked. 12/1/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No The pit shall be kept clean. 12/1/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No The pit lighting shall be operational. 12/1/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 12/1/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be obtained and displayed in the elevator machine room. 12/1/2021
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 12/1/2021
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) No No The car top shall be kept clean. 12/1/2021
A17.1-1996 : Elevators 4.2 - Hoistway doors 1001.2(d)(2) No No Replace the missing door gib on the 4th floor front hoistway door. 12/1/2021
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors Yes No The front and rear car door restrictors shall be operational. 8/31/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 8/31/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No The in car emergency lighting shall be operational. 8/31/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. The operating certificate is expired. 6/9/2026
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. The test is not being logged monthly. 6/9/2026
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No No An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. The fire extinguisher is expired. 6/9/2026
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No The pit light shall be operational. 6/9/2026
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 No No All machine room wiring shall be enclosed. There are several electric box covers missing. 6/9/2026
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b No No The machine room temperature shall be kept within the manufacturers recommended range. The machine room temperature is not being controlled. 6/9/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 6/9/2026
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No No A current ABC type fire extinguisher shall be provided in the machine room. 6/9/2026