Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 12/1/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room. 12/1/2021
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 12/1/2021
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) The car top shall be kept clean. 12/1/2021
A17.1-1996 : Elevators 4.2 - Hoistway doors 1001.2(d)(2) Replace the missing door gib on the 4th floor front hoistway door. 12/1/2021
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x The front and rear car door restrictors shall be operational. 10/12/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit shall be kept clean. 12/1/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit lighting shall be operational. 12/1/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 10/12/2021
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The in car emergency lighting shall be operational. 10/12/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x Phase 2 fire service shall operate properly. 10/12/2021
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) The machine room shall be provided with a natural or mechanical means to control temperature and humidity in the range specified by the elevator manufacturer. 12/1/2021
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) Access to the machine room door shall not be blocked. 12/1/2021
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x The front and rear car door restrictors shall be operational. 8/31/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 8/31/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The in car emergency lighting shall be operational. 8/31/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. The operating certificate is expired.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. The test is not being logged monthly.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. The fire extinguisher is expired.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit light shall be operational.
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 All machine room wiring shall be enclosed. There are several electric box covers missing.
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b The machine room temperature shall be kept within the manufacturers recommended range. The machine room temperature is not being controlled.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h A current ABC type fire extinguisher shall be provided in the machine room.