Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency two way communication device is inoperable 9/13/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No A fire extinguisher with a current inspection tag shall be provided in the machine room 4/7/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No The emergency generator testing shall be performed. Re-inspection required 9/2/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No The elevator would not respond to emergency power operation when the car selector switch was selected for this elevator. 4/7/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No The illuminated signal marked“ELEVATOR EMERGENCY POWER” did not activate when the facilities emergency generator back up power system was activated. Repair the illuminated signal to operate as required. Reinspect when repaired. 1/5/2022