Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency two way communication device is inoperable 9/12/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency two way communication device is inoperable. Repair or replace. 10/28/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A fire extinguisher with a current inspection tag shall be placed in the machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency generator testing shall be performed. Re-inspection required 9/2/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x The elevator would not respond to emergency power operation when the car selector switch was selected for this elevator.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x The illuminated signal marked“ELEVATOR EMERGENCY POWER” did not activate when the facilities emergency generator back up power system was activated. Repair the illuminated signal to operate as required. Reinspect when repaired. 1/5/2022