MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working. Re-inspection required
|
11/30/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working. Re-inspection required
|
1/29/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working. Re-inspection required
|
6/7/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Need to replace bad door hanger roller on 3rd floor
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Need to clean car top
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace bad door hanger roller on 3rd floor.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Need to clean car top.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace bad door hanger roller on 3rd floor.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Need to clean car top
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Repair all lighting in machine room to provide proper illumination
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to be cleaned
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)2
|
|
|
Pit channels, buffer supports, guide rails are rusted. Need to remove rust and apply inhibitor to prevent further damage or replace affected equipment.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)2
|
|
|
Pit channels, buffer supports, guide raills are rusted. Remove rust and apply inhibitor to prevent further damage or replace affected equipment.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)2
|
|
|
Pit channels, buffer supports, guide raills are rusted. Remove rust and apply inhibitor to prevent further damage or replace affected equipment.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to be cleaned.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to be cleaned
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Elevator did not respond to Fire Fighter's Phase I recall keyswitch in lobby. Red-tagged, Re-inspection reqired
|
11/30/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Elevator did not respond to Fire Fighter's Phase I recall keyswitch in lobby.Elevator is not able to operate on normal operation due to the door reopening device not being operational. Red-tag shall remain on elevator. Re-inspection and repair required.
|
1/29/2024
|
A17.1-2016 : Elevators
|
1.1 - Door Reopening Device
|
8.6.4.13.1(c)
|
x
|
|
Replace car door reopening device. Re-inspection required
|
1/29/2024
|
A17.1-2016 : Elevators
|
1.1 - Door Reopening Device
|
8.6.4.13.1(c)
|
x
|
|
Replace car door reopening device. Re-inspection required
|
11/30/2023
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
The car door restrictor device shall be repaired so that it will properly catch and restrict opening of the car doors to maximum of 4 inches when the car is away from the landing zone.
|
9/10/2019
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Lost phone signal. Repair
|
4/30/2021
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3a
|
|
|
Safe access to machine room shall be provided, repair lighting in stairway to roof.
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
Repair all lighting in machine room to provide proper illumination.
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
Repair all lighting in machine room to provide proper illumination.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Clean water and debris from elevator pit.
|
6/5/2020
|
A17.1-1996 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
1001.2(e)(2)
|
x
|
|
Shorten hoist cables for proper runby clearance.
|
8/19/2020
|