Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Clean water and debris from elevator pit. 6/5/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Lost phone signal. Repair 4/30/2021
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting No No Repair all lighting in machine room to provide proper illumination. 10/31/2025
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting No No Repair all lighting in machine room to provide proper illumination. 10/31/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Repair inoperative emergency phone
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3a No No Safe access to machine room shall be provided, repair lighting in stairway to roof. 10/31/2025
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 1001.2(e)(2) Yes No Shorten hoist cables for proper runby clearance. 8/19/2020
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) Yes No The car door restrictor device shall be repaired so that it will properly catch and restrict opening of the car doors to maximum of 4 inches when the car is away from the landing zone. 9/10/2019
A17.1-2016 : Elevators 1.1 - Door Reopening Device 8.6.4.13.1(c) Yes No Replace car door reopening device. Re-inspection required 11/30/2023
A17.1-2016 : Elevators 1.1 - Door Reopening Device 8.6.4.13.1(c) Yes No Replace car door reopening device. Re-inspection required 1/29/2024
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Elevator did not respond to Fire Fighter's Phase I recall keyswitch in lobby. Red-tagged, Re-inspection reqired 11/30/2023
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Elevator did not respond to Fire Fighter's Phase I recall keyswitch in lobby.Elevator is not able to operate on normal operation due to the door reopening device not being operational. Red-tag shall remain on elevator. Re-inspection and repair required. 1/29/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone is not working. Re-inspection required 6/7/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone is not working. Re-inspection required 1/29/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone is not working. Re-inspection required 11/30/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Need to clean car top 10/31/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Need to clean car top
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Need to clean car top. 10/31/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Need to replace bad door hanger roller on 3rd floor
MO Minimum : Elevators (I) - Pits (I)2 No No Pit channels, buffer supports, guide raills are rusted. Remove rust and apply inhibitor to prevent further damage or replace affected equipment.
MO Minimum : Elevators (I) - Pits (I)2 No No Pit channels, buffer supports, guide raills are rusted. Remove rust and apply inhibitor to prevent further damage or replace affected equipment. 10/31/2025
MO Minimum : Elevators (I) - Pits (I)2 No No Pit channels, buffer supports, guide rails are rusted. Need to remove rust and apply inhibitor to prevent further damage or replace affected equipment.
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned 10/31/2025
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned. 10/31/2025
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Repair all lighting in machine room to provide proper illumination
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace bad door hanger roller on 3rd floor. 10/31/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace bad door hanger roller on 3rd floor. 10/31/2025