Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. Re-inspection required 5/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Car emergency light shall work on aux power. Re-inspection required 5/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency alarm shall work on aux power. Re-inspection required 5/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Expired
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger unit from pit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger line from tank.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A copy of the MCP shall be kept in the machine room for each elevator
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger pump and line to tank
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide current fire extinguisher in machine room
MO Minimum : Elevators (I) - Pits (I)1 Clean pit
MO Minimum : Elevators (I) - Pits (I)1 Clean pit.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.3 Provide Auxiliary Lighting x Emergency lighting in the car not working on battery 5/9/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Not tested 6/10/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 8.11.2.1.1(h) x Front and Rear car doors exceed the 30 pound maximum closing force 5/9/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 8.11.2.1.1(h) x Not tested. 6/10/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 2.13.4.2.3 x Door closing forces on both sides exceed 30 ft/lbs. Re-inspection required 5/16/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Annual inspection incomplete. Must perform the testing of the stop ring and get a pressure. No prints on site
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is due for testing, need to perform test
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.31 - Relief Valves 8.11.3.1.2(n) 2nd tank not tested.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.31 - Relief Valves 8.11.3.1.2(n) Relief valve on left pump unit not functioning properly and not adjustible
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.2 Collection of Oil Leakage Scavenger pumps do not allow for documentation of the volume of cylinder head leakage
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) MCP not up to date.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Pit sump full of hydraulic fluid
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) x Not tested 6/10/2022