Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Suspension rope tail ends shall be properly seized/banded and retaining clips shall be set at proper distance. 4/13/2026
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/13/2026
A17.1-1996 : Elevators 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.4.10.1.2 - Protection not functioning Yes No 8.11.2.1.1(y) - Seismic "earthquake direction switch" shall be operational. 5/13/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/13/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/13/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/13/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current state operating permit shall be obtained and displayed in the equipment room. 4/13/2026
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Alarm bell shall work with loss of main 120v power. 3/14/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No 2-way communication device shall work. 9/11/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. This violation must be corrected immediately per the AHJ. 3/4/2025
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No Emergency lighting shall work. 3/14/2024
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 No No Cab lighting - All lamps shall work, none working. 4/13/2026
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No MCP fire service testing must be properly documented monthly on log sheet. 4/13/2026
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No MCP Fire Service testing must be properly documented monthly on log sheet. There is no log present. 4/13/2026
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No No Machine room shall have current tested and tagged fire extinguisher. No extinguisher in room or immediately adjacent to door. 4/13/2026
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors Yes No Car door restrictor shall work at all floors. 9/11/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No The wiring in the pit shall be enclosed. (Note: A box cover is missing) 4/13/2026
A17.1-1996 : Elevators 2.6 - Ventilation 102.4 No No The controller air conditioning shall be operational. 4/13/2026
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No A current tested ABC type fire extinguisher shall be provided in the elevator machine room. Current extinguisher is expired. 5/21/2020
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 4/13/2026
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) No No The controller air conditioning shall be operational. 4/13/2026
A17.1-1996 : Elevators 2.4 - Machine space 1001.2(b)(4) No No The elevator machine room shall be protected from the weather. (Note: Windows are being left open, and the equipment and machine room floor are showing signs that they have been wet, possibly from a leaky roof). 4/13/2026
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code No No All lighting in the machine room shall be operational. 5/21/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational on auxiliary power. 5/13/2022
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) No No The car identification number shall be painted on, engraved, or securely attached to the car operating panel and shall be a minimum of 1/2" in height. (Note: The COP should be identified as car 1 as it is in the machine room). 4/13/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing incomplete due to elevator operational failure. Needs: all tests that include weight, buffers, pit, fire service 1 & 2, runby. 9/1/2023