MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
2 way communication is not working. Re-inspection required
|
6/23/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Must make emergency phone Visual signal operable. 8.6.4.15
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.1 Emergency communications and alarm not functioning (Red Tag)
|
|
|
No operating emergency telephone.
|
5/27/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Must provide Code Data Plate. 8.9.1
|
12/9/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working. Re-inspection required
|
7/7/2022
|
A17.1-2016 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.5
|
|
|
Must replace/repair jack packing Gland to limit oil leakage. 8.6.5.5.1
|
|