MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
perform monthly fire service test and fill out the log in the machine room
|
10/8/2020
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.3.1.5(a)
|
|
|
missing cover on outlet in the pit
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
a copy of the state operating certificate is to be posted in the elevator machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the current year's state operating certificate is to be displayed in the machine room
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.3.1.5(a)
|
|
|
all of the sump pump equipment is to be plugged into the non-GFCI outlet that has been provided, the GFCI outlet is for the elevator technician use
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Replace burnt out pit lights
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1(a)(3) Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone did not work with the 110 volt power off, replace backup battery
|
6/8/2023
|