Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Must make emergency alarm operable. 8.6.4.15 4/15/2024
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) Yes No Must make Emergency Light operable. 8.6.4.15 4/15/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 Yes No Must test Fire service for proper operation (at the time of inspection Rear door lock was not function properly could not test Fire service)Re-inspection required once repair is made. 8..4.19. 4/15/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(c)(2) No No Must Preform and Doc. Monthly fire service testing. 8.6.2.1(c)(2) 12/6/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No Must Provide and Maintain all required MCP Documentation. 12/6/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit must be Kept Free of Debris. 12/6/2023
A17.1-2016 : Elevators 1.1 - Door Reopening Device 8.6.4.13.1(c) No No Must replace/repair broken door re-opening device Rubber boot to maintain proper operation. 8.6.4.13.1(c) 11/15/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Must Make Emergency phone operable.1.6
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.8 Switch Keys No No Must make Phase II Fire Service Key Switch operate properly. 211.8