Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)10 No No The lowest landing door to access the pit pull chain is broken and shall be repaired. 8/26/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No State of Missouri Minimum Elevator Safety Code Item from 11 CSR 40-5.065 G.1 - 8.6.4.15 Car Emergency Systems - The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. 8/28/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. 8/28/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Hoistway access pull chain box needs to be refastened at top landing 6/27/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency lighting shall be made operable. Re-inspection required 6/2/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Hoistway access pull chain box needs to be refastened at top landing 2/20/2026
conversion conversion n/a No No The elevator pit floor is covered in oil. The elevator pit shall be kept clean and dry. 9/10/2019
conversion conversion n/a No No The gland packing on top of the hydraulic cylinder has a large amount of oil present. The oil seepage and leakage is excessive indicating the gland packing shall be replaced. 9/10/2019