Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency lighting shall be made operable. Re-inspection required 6/2/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Hoistway access pull chain box needs to be refastened at top landing 6/27/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Hoistway access pull chain box needs to be refastened at top landing
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x State of Missouri Minimum Elevator Safety Code Item from 11 CSR 40-5.065 G.1 - 8.6.4.15 Car Emergency Systems - The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. 8/28/2020
conversion conversion n/a The elevator pit floor is covered in oil. The elevator pit shall be kept clean and dry. 9/10/2019
conversion conversion n/a The gland packing on top of the hydraulic cylinder has a large amount of oil present. The oil seepage and leakage is excessive indicating the gland packing shall be replaced. 9/10/2019
MO Minimum : Elevators (A) - Hoistways (A)10 The lowest landing door to access the pit pull chain is broken and shall be repaired. 8/26/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. 8/28/2020