MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
pit light shall work
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to perform test on car safeties (soft set) Re-inspection required. Tried to perform test, but elevator pit & bottom floor were underwater.
|
|
conversion
|
conversion
|
n/a
|
|
|
The elevator pit light switch in the pit have corroded due to the high humidity levels and is no longer reliable. Replace switch.
|
8/26/2020
|
conversion
|
conversion
|
n/a
|
|
|
The elevator pit stop switch in the pit have corroded due to the high humidity levels and is no longer reliable. Replace switch.
|
8/26/2020
|
conversion
|
conversion
|
n/a
|
|
|
The hoistway door interlock switches at the bottom landing have corroded due to the high humidity levels and are no longer reliable. Replace switches.
|
8/26/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)7
|
|
|
Replace rusted pit stop switch. Piping and wiring is rusted.
|
8/26/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Replace pit light switch. Rusted out. Recommend using water tight boxes and piping.
|
8/26/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required.
|
8/28/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required.
|
8/28/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
x
|
Unit did not close rear doors and return to main recall landing when returning to Phase 1 operation from Phase 2. Red tagged unit.
|
7/30/2021
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)2
|
x
|
x
|
car tractions before reaching top final limit switch. Red tagged. Repair same before returning to service.
|
9/19/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
perform following tests to complete inspection: fire service phase I and II, seismic (including "ring and string, which has bee bypassed as result of water in lower level previously), soft set safeties
|
9/19/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
x
|
x
|
Car tractions before reaching top final limit switch. Red-tagged, Re-inspection required
|
11/13/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to perform the following tests to complete inspection: fire service phase 1 & 2, seismic (including ring & string which has been by passed as result of water in lower level previously) soft set car safeties.
|
11/13/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to test car safeties (soft set). Re-inspection required
|
1/26/2024
|