Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a No No The elevator pit light switch in the pit have corroded due to the high humidity levels and is no longer reliable. Replace switch. 8/26/2020
conversion conversion n/a No No The elevator pit stop switch in the pit have corroded due to the high humidity levels and is no longer reliable. Replace switch. 8/26/2020
conversion conversion n/a No No The hoistway door interlock switches at the bottom landing have corroded due to the high humidity levels and are no longer reliable. Replace switches. 8/26/2020
MO Minimum : Elevators (F) - Electrical Switches (F)2 Yes Yes car tractions before reaching top final limit switch. Red tagged. Repair same before returning to service. 9/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) Yes Yes Car tractions before reaching top final limit switch. Red-tagged, Re-inspection required 11/13/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to perform test on car safeties (soft set) Re-inspection required.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to perform test on car safeties (soft set) Re-inspection required. Tried to perform test, but elevator pit & bottom floor were underwater.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to perform the following tests to complete inspection: fire service phase 1 & 2, seismic (including ring & string which has been by passed as result of water in lower level previously) soft set car safeties. 11/13/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to test car safeties (soft set). Re-inspection required 1/26/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No perform following tests to complete inspection: fire service phase I and II, seismic (including "ring and string, which has bee bypassed as result of water in lower level previously), soft set safeties 9/19/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No pit light shall work
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Replace pit light switch. Rusted out. Recommend using water tight boxes and piping. 8/26/2020
MO Minimum : Elevators (I) - Pits (I)7 No No Replace rusted pit stop switch. Piping and wiring is rusted. 8/26/2020
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes Yes Unit did not close rear doors and return to main recall landing when returning to Phase 1 operation from Phase 2. Red tagged unit. 7/30/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. 8/28/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. 8/28/2020