A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
Auxiliary Power fails to bring the car down and open the doors when normal power is removed.
|
6/26/2026
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
Auxiliary Power (battery lowering) fails to bring the car down and open the doors when normal power is removed. (Reinspect)
|
8/11/2026
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
Yes
|
No
|
When switching from Phase II back to Phase I, the elevator does not recall to the Phase I landing. (Reinspect)
|
8/11/2026
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
Yes
|
No
|
When switching from Phase II back to Phase I, the elevator does not recall to the Phase I landing.
|
7/23/2025
|
|
conversion
|
conversion
|
conversion - reinspect
|
Yes
|
No
|
Provide a car door restrictor system that covers the entire hoistway.
|
6/25/2018
|