Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Auxiliary Power fails to bring the car down and open the doors when normal power is removed.
conversion conversion conversion - reinspect x Provide a car door restrictor system that covers the entire hoistway. 6/25/2018
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x When switching from Phase II back to Phase I, the elevator does not recall to the Phase I landing. 7/23/2025