Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)6 No No Electric door eye ray power is connected to emergency light and bell 110V disconnect. Provide a separate power supply. 9/11/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display the current state operating certificate. 9/11/2020
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Post Phase 1 instructions on lobby near phase 1 switch. 8/29/2019
conversion conversion conversion - reinspect Yes No Electronic safe edges are not bypassed on Phase 1 fire recall. 6/21/2018