Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Auxiliary Power fails to bring the car down and open the doors when normal power is removed. UPS indicates a charged. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. |