Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate. 6/12/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams A legible copy of the schematics shall be kept in the machine room. 7/22/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 5/11/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Up to date operating certificate required in the machine room. 8/2/2023
MO Minimum : Elevators (H) - Machine Rooms (H)9 x Each elevator having polyphase alternating current power supply shall be provided with means to prevent the starting of the elevator motor if: (A) the phase rotation is in the wrong direction; or (B) there is a failure of any phase.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x A Roust-a-bout fitting located below the hydraulic tank is leaking and shall be replaced with an approved grooved or threaded fitting (Roust-a-bout fittings are no longer allowed on elevators).
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The plunger gripper is due to be tested with a full load this year.
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 (Re-Inspection) x The pump motor belts shall not slip under load.