Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x 1/7/21 : 2-way communication device shall work and give proper location 9/25/2023
MO Minimum : Elevators (I) - Pits (I)1 1/7/21 Pit shall be kept dry. Remove rust from pit channels, repaint, repair water leak.
MO Minimum : Elevators (I) - Pits (I)5 1/7/21 Pit Ladder shall be installed
MO Minimum : Elevators (I) - Pits (I)5 Must provide permatly installed pit ladder. (I)5
MO Minimum : Elevators (I) - Pits (I)5 Must provide perminently installed pit ladder. (I)5
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) 1/7/21 Pit light shall work
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits I-1 Mo Min pit needs to be dry and clean 3/30/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Must Post current state operating Cert. 5.100(2)
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Telephone will not call out-52 volts on line 7/26/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) x Must make Car return to proper land after turning off Phase two Key switch. 6.4
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x 1/7/21 : Phase 2 switch not working. Repair/Replace REINSPECTION REQUIRED (14days) 9/25/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Must make Emergency Phone operable. 8.6.4.15 8/22/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Pit Must be kept free of water ( currently 1" standing water in pit). 8.6.4.7
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Pit must be kept free of Water 8.6.4.7
conversion conversion conversion - reinspect x telephone not working--REINSPECT REQUIRED 7/23/2018
conversion conversion n/a pit light not working 3/30/2020
conversion conversion n/a pit has water & oil standing pit needs to be dry and clean 3/30/2020
conversion conversion n/a needs current certificate posted in machine room 3/30/2020