Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.16 - Rated load, platform area, and data plate 2.16 x Correct the capacity plate on the COP. Currently says 2500 lbs. and the actual capacity is 2000 lbs. 1/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.1.1 x 2.7.1.1.2 - The machine room door shall have a fire rating of 1.5 hours. 1/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.1.1 x Seal all penetrations in the machine room. 1/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 (Re-Inspection) x Finish the installation of the sprinkler head in the machine room. 1/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 x Seal all penetrations in the hoistway. 1/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 x Complete the construction of the top of the hoistway. 1/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Install all covers on junction boxes and wiring ducts in the hoistway. 1/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Finish the installation of the sprinkler head at the top of the hoistway. 1/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x A sprinkler head shall be installed in the pit. 1/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures x Install all fire service signage and do not use in case of fire signage. 1/3/2020