ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.4 - Machine space
|
2.7.1.1
|
x
|
|
Seal all penetrations in the machine room.
|
1/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
A current tested, ABC type fire extinguisher shall be provided in the machine room.
|
1/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2 (Re-Inspection)
|
x
|
|
Pipes conveying gases, vapors, or liquid shall not be installed in the machine room. Verify contents of pipes over controller and disconnect. Guard as required.
|
1/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Seal all penetrations in the hoistway.
|
1/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Finish the installation of the sprinkler head at the top of the hoistway.
|
1/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Install all covers on junction boxes and wiring ducts in the machine room and hoistway.
|
1/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
2.4
|
x
|
x
|
Top of car clearance shall be code compliant.
|
1/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump pump shall be provided
|
x
|
|
Finish the sump pump.
|
1/3/2020
|